| Brand Name | Ferrob |
| Model | Infinity 9000 |
| Model Qualifier (if applicable) |
| | Current Manufacturer and Contact Details | Name | Ferrob Ltd |
Address | Regency House
Kingsclere Park
Kingsclere
Newbury
Berks
RG20 4SW |
Telephone | 01635 296 716 |
Website | www.ferrob.co.uk |
| Original Manufacturer (if different) | |
| First Year of Manufacture | 2010 |
| Last Year of Manufacture | |
| Testing Body | BRE |
| Date of test | 22/03/2010 |
| Serial Number of Product Tested | 5780 EC |
| MVHR to outside grille duct types and size | 150 & 125 mm diameter rigid plastic and 200 mm diameter rigid plastic |
| Duct types and sizes used for supply and exhaust | 150 & 125 mm diameter rigid plastic and 200 mm diameter rigid plastic |
Results of leakage tests
Table Q1
| Internal |
Pass |
| External |
Pass |
Results for SAP calculations (at minimum flow rate condition)
Table Q2 – Systems with rigid ductwork installation only
This product has only been tested with rigid ductwork and the data are not applicable for SAP calculations if installed with flexible ductwork. |
Exhaust terminal configuration | Fan speed setting | Specific fan power (W/l/s) | Heat exchange efficiency (%) | Energy Saving Trust Best Practice Performance Compliant |
Kitchen + 1 additional wet room | 100% Variable | 0.73 | 91 | Yes |
Kitchen + 2 additional wet rooms | 100% Variable | 0.72 | 90 | Yes |
Kitchen + 3 additional wet rooms | 100% Variable | 0.79 | 89 | Yes |
Kitchen + 4 additional wet rooms | 100% Variable | 0.93 | 88 | Yes |
Kitchen + 5 additional wet rooms | 100% Variable | 1.06 | 87 | Yes |
These figures are entered into either:
(a) In the case of SAP software amended to SAP 2005 version 9.81 allowing direct
entry of MVHR data, the SAP software, or
(b) In the case of SAP software amended to SAP 2005 version 9.81 not allowing
direct entry of MVHR data, the SAP Q MVHR Calculation Spreadsheet v9.81 and
the results from the spreadsheet into the Special Features part of the SAP 9.81
software, or
(c) In the case of SAP software to SAP 2005 version 9.80 , the SAP Q MVHR
Calculation Spreadsheet v9.80 and the results from the spreadsheet into the
Special Features part of the SAP 9.80 software. They must NOT be entered
directly into SAP 2005 version 9.80 software |
Results for Approved Document F (at minimum flow rate condition)
Table Q2 – Systems with rigid ductwork installation only
Table Q3 – Systems with flexible ductwork only
Exhaust terminal configuration | Fan speed setting | Specific fan power (W/l/s) | Heat exchange efficiency (%) | Energy Saving Trust Best Practice Performance Compliant |
Kitchen + 1 additional wet room | N/A | N/A | N/A | N/A |
These figures are entered into either:
(a) In the case of SAP software amended to SAP 2005 version 9.81 allowing direct
entry of MVHR data, the SAP software, or
(b) In the case of SAP software amended to SAP 2005 version 9.81 not allowing
direct entry of MVHR data, the SAP Q MVHR Calculation Spreadsheet v9.81 and
the results from the spreadsheet into the Special Features part of the SAP 9.81
software, or
(c) In the case of SAP software to SAP 2005 version 9.80 , the SAP Q MVHR
Calculation Spreadsheet v9.80 and the results from the spreadsheet into the
Special Features part of the SAP 9.80 software. They must NOT be entered
directly into SAP 2005 version 9.80 software |
Results for Approved Document F (at maximum flow rate condition)
Table Q4
Exhaust terminal configuration | Fan speed setting | Total exhaust flow rate (l/s) | Total supply flow rate (l/s) |
Kitchen + 1 additional wet room | 100% Variable | 15.0 | 15.0 |
Kitchen + 2 additional wet rooms | 100% Variable | 21.0 | 21.0 |
Kitchen + 3 additional wet rooms | 100% Variable | 27.0 | 27.0 |
Kitchen + 4 additional wet rooms | 100% Variable | 33.0 | 33.0 |
Kitchen + 5 additional wet rooms | 100% Variable | 39.0 | 39.0 |
Comments
Only figures from Table Q2 or Table Q3, not both, should be used with the SAP Q
Calculation Spreadsheet for this technology type.
Table Q4 results are only applicable for Approved Document F requirements.
|